LC to LC fiber testing with the SimpliFiber Pro

The following article describes how to test an LC to LC fiber link using TIA/EIA Method B for Multimode and TIA/EIA Method A.1 for Singlemode. 
You may hear people referring to this as the "1 jumper method". To confuse matters, the IEC Standards call it Method 2 for Multimode and Method A1 for Singlemode, as shown in the table below:
 

You will need:

  • Power on the SimpliFiber Pro Source.
  • Press the AUTO key on the SimpliFiber Pro Source .
  • In AUTO mode, the SimpliFiber Pro Source will tell the SimpliFiber Pro Meter which wavelength it is transmitting at. This allows both wavelengths to be measured at the same time.

  • Leave the SimpliFiber Pro Source to stabilize for at least 5 minutes.
  • While the SimpliFiber Pro Source is stabilizing, clean and inspect your test reference cords.
  • Replace the SC Interchangeable Adapter with the LC Interchangeable Adapter.

  • Connect your test reference cord as shown below, making sure the fiber size is the same as the link you are about to test. 

  • Press the Mode key until you see LOSS in the upper right hand screen (shown below).

  • Press the F3 key once to set the reference. When you see OK appear, the reference has been set for both wavelengths.
  • If the SimpliFiber Pro Source has been allowed to stabilize fully, you should see 0.00 dB as shown below:

  • If you start to see it change from 0.00 dB, it means the SimpliFiber Pro Source has not been allowed to stabilize. Wait until the reading stabilizes, then press the F3 key again to reset the reference.
  • Remove the reference patch cord from the INPUT PORT ONLY on the SimpliFiber Pro Meter.

  • Put a known good LC to LC test reference cord into the INPUT port on the SimpliFiber Pro Meter.

  • Connect to the fiber link to be tested. 